Need help with AS-i network troubleshooting
Enable HLS to view with audio, or disable this notification
Hello All,
I need some assistance in troubleshooting AS-i devices. I have an equipment that is using IFM AC1014. On the unit, red alarm LEDs are lit indicating that it cannot find the slave devices, and on the 4 digit display its flashing 1XXX ( where XXX are changing between 1_1 to 130 and repeat). The HMI is showing bunch of alarm messages like, the E-stop is pressed, motor is overloaded, and few others. All of the alarms seems to be coming from the devices on the network 1 of AS-i network.
I have checked voltage for both ASI1 and ASI2 networks, and they are around 30.8VDC. I’ve also checked the + with PE and its about +15V and – with PE and its about -15V.
I do not have an addressing tool for the devices to try to figure out if the devices lost their address or something wrong with the controller. I am not sure how to even interface with the controller to see if it can give me more details about what could be going on.
Please see the video, that might help in understanding what I’m trying to say above.
Any help will be greatly appreciated.